handle position to be up and the OFF handle
position to be down.

• If plug-assist has been furnished on the plug,

the operating handle may be used as a

wrench to operate the mechanism.

• To install a plug where the rear plug hanger

interferes with a joint cap, it is necessary to
remove the break-off tabs, as shown in the
Figure 2.

• On large plugs, drop rod brackets are

provided for auxiliary support of the plug on
the horizontal runs.

CAUTION: Make certain that the bus plug is level

in all orientations with the busway after all

connections are completed. Failure to level the

plug could result in overheating of the plug

connection.

Installing a Plug Not Equipped with Plug-Assist

1. Make sure the device is in the OFF position.
2. Loosen the four bolts on the hanger hooks.
3. Align the actuator bar of the bus plug with the

vertical actuator bar slot on the shutter and
push firmly, the shutter will open and the bus

plug stabs fingers will engage the bus bars.

4. Push the stabs into the full contact with the

busway.

5. Engage the four hanger hooks with the

busway rails and tighten the bolts.

Installing a Plug Equipped with the Plug-Assist
1. Make sure the device is in the OFF position

and the plug-assist indicator is rotated fully

toward the stabs-OUT position.

2. Loosen the four bolts on the hanger hooks.
3. Align the actuator bar of the bus plug with the

vertical actuator bar slot on the shutter and
attach the line end hanger hooks to the bus

rail and tighten.

4. Recheck alignment of actuator and vertical

slot and attach load end hanger hooks to bus
rail and tighten.

5. Engage bus plug by rotating the plug assist

mechanism, the shutter should open and the
bus stab fingers will engage the bus bars. The
pointer should

indicate “Stabs-IN”.

NOTE: On the vertically mounted plugs, push up

on the plug to remove the weight of the plug

from the alignment pin before tightening the

bolts in step 4.

WARNING: Be sure that the plug-assist pointer is

lined up with the IN position before turning the

plug on. Failure to do so may result in serious

injury or death.

Removing a Plug
First turn the device OFF. Then follow the

appropriate procedure above in reverse order.



These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that

may be met in connection with installation, operation, or maintenance. Should further information be desired or should

particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE

Company.

GE Consumer & Industrial

41 Woodford Avenue

Plainville, CT 06062

www.geelectrical.com

DEH-40096A (04/07)