DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.


3. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front

cover as shown in Fig. 1.C.

Figure 1. (A) Front Cover (B) Screw Removal (C) Handle
Rotation


4. Slide the RTC switch assembly over the

mechanism side sheet and locate in the two
locating holes as shown in fig 2.

Figure 2. Assembly on mechanism


5. Assemble the screw with washer as shown in
Fig. 3 Tighten the screw to torque 1.2Nm (0.9 ft-
lbs).

Figure 3. Screw assembly

6. When RTC thru trip unit is used, plug the
connector from the RTC switch assembly to the
connector marked as RTC from the harness of the
trip unit as shown in Fig. 4.

Figure 4. Connector Plug Assembly


7. If RTC is used thru the secondary disconnect,

then first unplug the spring charge contact
connector from motor as shown in Fig. 5

Figure 5. Unplug Spring Contact


7. Plug the connector from the RTC switch
assembly with the plug marked as RTC as shown

in fig 6.