GE Industrial Solutions ProTrip Conversion Kits DB-15 User Manual

Page 12

Advertising
background image

Installing the Trip Unit

1. Place a lock washer and flat washer over each of the

three

1

/

4

-20 x 1

3

/

8

" screws provided and insert

through the mounting holes on the trip unit mounting
plate. From the rear of the plate, place a flat washer,
spacer, and O-ring over the screws, as shown in
Figure 17.

2. Remove the large screw from the rear of the trip unit.

Place the trip unit in position on the mounting plate,
with the 50-pin connector aligned with the opening in
the plate. Secure with the large screw, as shown in
Figure 17.

3. Insert the 50-pin female connector on the wiring

harness into the trip unit connector through the rear
of the mounting plate. Secure to the mounting plate
with the two small screws provided, as shown in
Figure 18.

Figure 18. Harness connector attached to the trip unit.

4. Place the trip unit and mounting plate in position on

the support bracket mounted to the breaker. Secure
with the screws in the mounting plate into the tapped
holes in the bracket, as shown in Figure 19.

Figure 19. Mounting the trip unit on the breaker.

Figure 17. Trip unit attached to its mounting plate.