Car2512fp series rectifier, Data sheet, Input: 90v – GE Industrial Solutions CAR2512FP Front-End User Manual

Page 6: Output: 12 v, Or 5 v, Environmental specifications, Emc compliance

Advertising
background image

GE

Data Sheet

CAR2512FP series rectifier

Input: 90V

AC

to 264V

AC

; Output: 12 V

DC

@ 2500W; 3.3V

DC

or 5 V

DC

@ 1A

April 23, 2013

©2013 General Electric Company. All rights reserved.

Page 6

Environmental Specifications

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature

-10

5

70

°C

Derated above 50C

Storage Temperature

-40

85

°C

Operating Altitude

2250/7382

m/ft

Non-operating Altitude

8200/30k

m / ft

Power Derating with Temperature

2.5

%/°C

50C to 70C

Power Derating with Altitude

2.0

C/301 m

C/1000 ft

Above 2250 m/7382 ft

Acoustic noise

55

dbA

Full load

Over Temperature Protection

125/110

°C

Shutdown / restart

Humidity
Operating
Storage

30
10

95
95

%

Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3, 20 -
2000Hz, min 30 minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic
Zone 4 Designed and tested to meet
NEBS specifications.


EMC Compliance

Parameter

Criteria

Standard

Level

Test

AC input

Conducted emissions

EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2

A* 0.15

30MHz

0 – 2 KHz

Radiated emissions**

EN55022

A*

30 – 10000MHz

AC input
immunity

Voltage dips

EN61000-4-11

B

-30%, 10ms

B -60%,

100ms

B -100%,

5sec

Voltage surge

EN61000-4-5

A

4kV, 1.2/50µs, common mode

A

2kV, 1.2/50µs, differential mode

Fast transients

EN61000-4-4

B

5/50ns, 2kV (common mode)

Enclosure
immunity

Conducted RF fields

EN61000-4-6

A

130dBµV, 0.15-80MHz, 80% AM

Radiated RF fields

EN61000-4-3

A

10V/m, 80-1000MHz, 80% AM

ENV 50140

A

ESD

EN61000-4-2

B

4kV contact, 8kV air

*

Note: Contact the factory for a recommended external EMI filter to meet Class B emissions

**

Radiated emissions compliance is contingent upon the final system configuration.

5

Designed to start at an ambient down to -40°C; meet spec after  30 min warm up period, may not meet operational limits below -10°C.