For Two-Pole Devices on Three-Phase

Systems Only

To balance the panelboard load, remove the screws on the

appropriate bus clip, reposition the bus clip as shown in

Figure 8, then reinstall and tighten the screws to 27–32 in-

lb.

Figure 8. Repositioning the bus clip to balance the load.

A & C Phase
As Received

A & B Phase

B & C Phase

Advertising