GE Industrial Solutions EntelliGuard G Drawout Secondary Disconnect User Manual

Entelliguard

Advertising
background image

Introduction
Drawout Secondary Disconnect:

Drawout breakers are always supplied with one
secondary disconnect (auxiliary connection block)
suitable for 39 connection points (terminal A).
When the number of factory installed accessories

exceeds the available number of connection
points needed, a 2

nd

connection block is

automatically added (terminal B) to the Breaker.
For cases where the accessories are mounted in
the field, or needed for the cassette an additional

auxiliary connection block can be added to
provide 39 more additional connections.

Figure 1. SD Breaker End

Figure 2. SD Cassette End














Catalog Number:

Catalog No Description
GSDWTR

Aux, Disconnect Drawout 39
terminal


Use the following procedure to install the
Drawout Secondary Disconnect accessory into
the circuit breaker.

Installation of Breaker side Secondary
disconnect:

1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in

the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from

adaptor (cassette) before continuing.

2. The breaker should be safely isolated and fully
removed from the cassette.


3. Place the secondary disconnect block on the
mounting bracket and assemble the two
mounting screws as shown in fig 3 & 4

.

EntelliGuard

®

G Circuit Breaker

Accessories

Drawout Secondary Disconnect

WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement

DEH-41401 Installation Instructions