GE Industrial Solutions SPSA600 User Manual

Power supply plate, Geh-6251 installation instructions, Ge energy industrial solutions

Advertising
background image

GEH-6251 Installation Instructions

Power Supply Plate

For Spectra

®

RMS Molded-Case Circuit Breakers with microEntelliGuard

TM

,

MicroVersaTrip

®

PM or MicroVersaTrip

®

Plus Trip Units

For Catalog Numbers SPSA120, SPSA208, SPSA240, SPSA480, SPSA600

Circuit Breaker Accessory

Overview
The General Electric Power Supply Plate is used to
provide +24Vdc Control Power to Spectra

®

RMS Molded-

Case Circuit Breakers with microEntelliGuard

TM

or

MicroVersaTrip

®

PM/Plus Trip Units via the Distribution

Cable System. The Power Supply Plate also provides
power to the Voltage Conditioner Assembly or Voltage
Conditioner Plate (Spectra

®

RMS Molded-Case Circuit

Breakers with microEntelliGuard

TM

or MicroVersaTrip

®

PM Trip Units require connection to a Voltage
Conditioner Assembly or Voltage Conditioner Plate to
function properly). The Power Supply Plate includes the
Power Supply Assembly (catalog number SPSAA) as an

integral component and also includes fuse protection
for the AC source input terminals.

The Power Supply Plate is rated 24 watts (+24Vdc @
1.0 Amp) and has the maximum capacity to power a
Distribution Cable System consisting of either a Voltage
Conditioner Assembly or a Voltage Conditioner Plate
AND 20 Spectra

®

RMS Molded-Case Circuit Breakers

with microEntelliGuard

TM

or MicroVersaTrip

®

PM / Plus

Trip Units with a maximum system cable length of 40
feet. The Power Supply Plate is designed to operate in
temperatures between O°C and 70°C.