GE Industrial Solutions Power Express Class 2 User Manual

Page 2

Advertising
background image

Step 4 - Connect DC Outputs

Step 5 - Connect Alarm Cable

 Remove alarm connector from the chassis.

 Connect alarm cable.

 Insert alarm connector into the chassis.

Step 3 - Verify DC Input Voltage and Polarity

Wire Entry

24 - 8 gauge

Warning: Shock Hazard and Equipment Damage - Equipment and subassembly ports

1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.

DC Output Return Terminals

(-48V DC Return / Ground)

DC Output Terminals

(-48V DC)

Connect DC Output and DC Output Return wires for each output.

32 DC Outputs - 8 per Module.

Release hole (#0 Phillips or 1/8” flat screw driver)

To Remove a wire:

Push the screw driver into release hole at a

downward angle.

Pull the wire out of the terminal.

Wire entry

28 - 16 gauge

Screw (1/16” flat screw driver)

 Strip wire 3/16”

 Insert wire fully into wire entry

 Tighten screw

Close On Alarm - COA

Open On Alarm - OOA

Common - COM

 Strip wire 1/2”

 Insert wire fully into wire entry

 Pull wire to verify insertion.

Alarm Connector Location

Verify that the DC Input voltage is -48VDC and matches the marked polarity using a meter.

Note: Equipment will operate properly only with proper DC Input voltage and polarity.

-48 V DC

(DC Input Battery)

Step 6 - Verify Shelf ID Setting

Shelf ID 00 operate without a system controller.

Shelf ID 99 performs Lamp Test.

Ground

(DC Input Return)

Power Express - Quick Start Guide

Document 850031168 r05 2013 December

2

Module 4

Module 3

Module 2

Module 1

Advertising