Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection: Circuits are scanned for loads upon module power up and upon manual scan.

Circuits with loads are turned ON, circuits without loads are turned OFF.

Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/OFF state of each circuit.
The only automatic change in circuit ON/OFF status occurs upon module power up.

Information: Circuit ON/OFF and Load Detection

Manually Scan Circuit Loads: Press and release the Button - no interruption of power to ON circuits.
Manual Circuit ON/OFF:

1. Press and hold the Button to enter the manual mode

hold until the OK LED turns OFF and back ON (2 seconds)

2. Tap the Button repeatedly until the desired Circuit LED blinks
3. Press and hold the Button to toggle the circuit ON/OFF

hold until the OK LED turns OFF and back ON (2 seconds)

4. Repeat from step 2 to operate another circuit
5. Automatic operation is restored after a few seconds of Button inactivity

The OK LED is turned OFF when the button is pressed. It returns to ON when the button is released or after the

button is held for 2 seconds.

Information: Manual Module Operations

Button

Circuit LEDs

Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection: Circuits are scanned for loads upon module power up and upon manual scan.

Circuits with loads are turned ON, circuits without loads are turned OFF.

Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/OFF state of each circuit.
The only automatic change in circuit ON/OFF status occurs upon module power up.

Information: Fault Detection

Specifications and Application


Specifications and ordering information are in the Power Express Class 2 Distribution Brochure available at

www.gecriticalpower.com



External Surge Protective Device (SPD) is required on all AC inputs.



Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;

2. can be connected to shielded intra-building cabling grounded at both ends.



Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane

(Mesh Bonding Network or Common Bonding Network).



Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.



Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).

Reference Documents

These documents are available at

www.gecriticalpower.com

.

Document Title

Power Express Class 2 Distribution Brochure (aka Power Express Class 2 Distribution Ordering Guide )

Circuit LED Blink Pattern

ON

ON with brief blink OFF

OFF

OFF with brief blink ON

Power Express - Quick Start Guide

Document 850031168 r05 2013 December