Ge energy, Car1612fp series rectifier – GE Industrial Solutions CAR1612FP series User Manual

Page 3

Advertising
background image

GE Energy

CAR1612FP series rectifier

Input: 85Vac to 264Vac; Output: 12 Vdc @ 1600W; 3.3Vdc or 5 Vdc @ 1A

November 1, 2012

©2012 General Electric Company. All rights reserved.

Page 3

12V

dc

MAIN OUTPUT (continued)

Parameter

Device

Symbol

Min

Typ

Max

Unit

Remote ON/OFF delay time

All

40

ms

Turn-ON rise time (10 – 90% of V

out

)

50

ms

Transient response 50% step [10%-60%, 50% - 100%]

(dI/dt – 1A/µs, recovery 300µs)

V

out

-5 +5

%V

out

Programmable range (hardware

4

& software)

10.8

13.2

V

dc

Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)

13.8 14.8 15.8 V

dc

Output current V

in

= HL

V

in

= LL

I

out

0

134
100

A

dc

Current limit, Hiccup (programmable level)

110

130

% of FL

Active current share

-5

+5

% of FL

AUXILIARY OUTPUT

Parameter

Device

Symbol

Min

Typ

Max

Unit

Set point

All

V

out

3.3

/

5.0 V

dc

Overall regulation (load, temperature, aging)

All

-5

+5

%

Ripple and noise

All

50

mVp-p

Output current

All

I

out

0 1

A

dc

Overload protection -

1.1 2.6

A

dc

Overvoltage protection

Isolation Output/Frame

All

100

V

dc

Environmental, Reliability

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature
Operating
Altitude Operating
Power Derating

-10

5

70

6

2250

2.5

°C

m

%/°C


Air inlet from sea level to 5,000 feet.
7400 ft
51°C to 70C (60C max where TUV/VDE is required)

Storage
Altitude non-operating

-40

85

8200

°C

m


30,000 ft

Overload Protection shutdown
restart

125

110

°C

Humidity Operating

Storage

30
10

95

95

%

Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3, 20 -2000Hz, minimum 30 minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and

tested to meet NEBS specifications.

Reliability 25C

320,000

Hrs

Full load, MTBF per Bellcore RPP

50C

100,000

Hrs

Full load, MTBF per Bellcore RPP

200,000

Hrs

Full load, demonstrated MTBF

4

V

out

=10.8 + (V

prog

* 0.96) where 0 < V

prog

< 2.5. Unit stays at 13.2V when 2.5 < V

prog

< 3. Unit stays at 12V when V

prog

> 3V or no-connect.

5

Designed to start at an ambient down to -40°C; meet spec after  30 min warm up period, may not meet operational limits below -10°C.

6

60C max where TUV/VDE is required