Absolute maximum ratings, Electrical specifications – GE Industrial Solutions Austin MegaLynx User Manual

Page 2

Advertising
background image

Data Sheet
April 19, 2011

Austin MegaLynx

TM

: Non-Isolated DC-DC Power Modules:

4.5 – 5.5Vdc input; 0.8 – 3.63Vdc output; 30A output current

6.0 – 14Vdc input; 0.8 – 5.5Vdc output; 25A output current

LINEAGE

POWER

2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are
absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in
excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for
extended periods can adversely affect the device reliability.

Parameter

Device

Symbol

Min

Max

Unit

Input Voltage

Continuous

All

V

IN

-0.3 15 Vdc

Sequencing pin voltage

All

Vs

EQ

-0.3 15 Vdc

Operating Ambient Temperature

All

T

A

-40 85 °C

(see

Thermal

Considerations

section)

Storage Temperature

All

T

stg

-55 125 °C

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Operating Input Voltage

ATH

V

IN

4.5 5.0 5.5

Vdc

ATS

V

IN

6.0

12

14

Vdc

Maximum Input Current

ATH

I

IN,max

27

Adc

(V

IN

= V

IN,min

, V

O

= V

O,set,

I

O

=I

O, max

) ATS

I

IN,max

26

Adc

Inrush Transient

All

I

2

t

1

A

2

s

Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 1μH source impedance;
V

IN

=6.0V to 14.0V, I

O

= I

Omax

; See Figure 1)

All

100

mAp-p

Input Ripple Rejection (120Hz)

All

50

dB


Advertising