Ge energy, Car2024fp series rectifier – GE Industrial Solutions CAR2024FP series User Manual

Page 6

Advertising
background image

GE Energy

CAR2024FP series rectifier

Input: 90Vac to 264Vac; Output: 24 Vdc @ 83A; 3.3Vdc or 5 Vdc @ 1A

March 28, 2013

©2012 General Electric Company. All rights reserved.

Page 6

LEDs

Three LEDs are located on the front faceplate. The AC
LED provides visual indication of the INPUT signal
function. When the LED is ON GREEN the power supply
input is within normal design limits.

The second LED DC provides visual indication when the
output is ON. When the LED is GREEN then the DC
output is present.

The third LED FLT provides visual indication when a fault
is present. When the LED is RED then a fault condition
exists and the power supply does not provide output
power.

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

AC OK

DC OK

FAULT

FAULT

DC OK

INPUT OK

TEMP OK

1 Normal

Operation

Green

Green

OFF High High High High

2

Low or NO INPUT

OFF

OFF

Red

Low Low Low High

3 OVP

Green

OFF

Red

Low Low High High

4 Over

Current

Green

OFF

Red

Low Low High High

5

Over Temp Alarm

Green

Green

OFF High High High

Low

6

Over Temp Fault

Green

OFF

Red

Low Low High Low

7

Remote ON/OFF, OFF

Green

OFF

Red

Low Low High High


Note: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.

Outline Drawing

Advertising