GE Industrial Solutions EntelliGuard G Electrical close switch User Manual

Entelliguard, G circuit breaker, Accessories

Advertising
background image

Introduction
Electrical close switch:

Electrical close switch is an optional accessory
which can be used in combination with the
command Close coil. It has an extra ‘ON’ push
button that fits onto the breaker front fascia,

which can be locally operated manually to close
the breaker.

Figure 1.

Catalog Number: GECPR

Table 1.

Electrical close switch push button can be

used with the below Command close coils

Catalog No

DC Voltage

AC Voltage

GCCC024DR

24V

GCCC030DR

30V

GCCC048R

48V

48V

GCCC060DR

60-72V

GCCC120R

110-130V 110-130V

GCCC208AR

208V

GCCC240R

220-240V 220-240V









DEH-41374 Installation Instructions


EntelliGuard

®

G Circuit Breaker

Accessories


Electrical close switch




WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.



AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement


Use the following procedure to install the
Command Closing Coil accessory into the circuit

breaker.

1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the

breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from

adaptor (cassette) before continuing.

2. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the

front cover over the handle to remove the front
cover as shown in Fig. 1.C.


1