8. Insert the push button and the spring from the
front of the fascia. Assemble them to the fascia

with the screw & washer as shown in fig 8.

Figure 9.

10. Ensure the fascia is aligned properly with the
trip unit and the pad lock features of the breaker.


11. Fasten the 6 mounting screws of fascia with

the housing using a pozidrive screwdriver. Apply
torque of 6 Nm (4.42ft-lbs).




Fig 8. Push button assembly

9. To reinstall the cover, rotate the charging
handle down and slide the front cover over the

handle to assemble the front cover to housing as
shown in Fig. 9.