Af-650 gp – GE Industrial Solutions AF-650 GP Resolver Module User Manual

Page 2

Advertising
background image

AF-650 GP

TM

*MI33M122*

130R0142

DET-638

LED Indicators

LED 1 is on when the reference signal is OK to resolver
LED 2 is on when Cosinus signal is OK from resolver
LED 3 is on when Sinus signal is OK from resolver

The LEDs are active when par. EC-61 is set to Warning

or Trip.

Set-up example

In this example a Permanent Magnet (PM) Motor is used with the resolver as speed feedback. A PM motor must
usually operate in flux mode.
Wiring:

The max. cable length is 150 m when a twisted pair type of cable is used.

NOTE!

Resolver cables must be screened and separated from the motor cables.

NOTE!
The screen of the resolver cable must be correctly connected to the de-coupling plate and

connected to chassis (earth) on the motor to meet European EMC Standards.

NOTE!

Always use screened motor cables and brake chopper cables.

Par. H-40

Configuration Mode

Speed closed loop [1]

Par. H-41

Motor Control Principle

Flux with feedback [3]

Par. P-20

Motor Construction

PM, non salient SPM [1]

Par. P-03

Motor Current

Nameplate

Par. P-06

Motor Nominal Speed

Nameplate

Par. P-42

Motor Contr. Rated Torque Nameplate

Par. P-37

d-axis Inductance (Ld)

Motor data sheet (mH)

Par. 1-39

Motor Poles

Motor data sheet

Par. P-40

Back EMF at 1000 RPM

Motor data sheet

Par. P-41

Motor Angle Offset

Motor data sheet (Usually zero)

Par. RS-50

Poles

Resolver data sheet

Par. RS-51

Input Voltage

Resolver data sheet

Par. RS-52

Input Frequency

Resolver data sheet

Par. RS-53

Transformation Ratio

Resolver data sheet

Par. RS-59

Resolver Interface

Enabled [1]

Adjust following parameters:

Auto Tune (Par. P-04) is not available for use on permanent magnet motors.

The instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection
with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered suffi-
ciently for the purchaser's purposes, the matter should be referred to the GE company.

AF-650 GP is trademark of the General Electric Company.

GE consumer & Industrial
41 Woodford Avenue
Plainville, CT 06062

www.geelectrical.com/drives

Advertising