GE Industrial Solutions Spectra Series Power Panelboards 60 A_600 V, 100 A_240 V, 100 A_600 User Manual

Spectra series™ power panelboards, Installing the expansion kit

Advertising
background image

g

Spectra Series™ Power Panelboards

60 A/600 V, 100 A/240 V, 100 A/600 V Expansion Kits for

Type ADS Fusible Switch Units

WARNING: Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the

equipment or removing any component

.

Do

not remove circuit protective devices or any

other component until the power is turned

OFF.

Installing the Expansion Kit

1. Remove the fusible switch unit from the panelboard

or switchboard. Remove the load-side wires from the

switch load-side terminal. Loosen the rail latch

screws on each side of the switch unit and remove

the switch by pulling up on both latch handles, as

shown in Figure 1, while pulling the device from the

panelboard.

2. Prepare the enclosure. Remove and discard the

blank cover and the bottom insulator from the

bottom of the device, as shown in Figure 2.

3. Install the straps. Install the connecting straps with

the #10-32 x

1

/

2

" mounting screws provided, as

shown in Figure 3. Tighten the screws to 27–32 in-lb.

Figure 1. Removing the fusible switch from the equipment.

Figure 2. Removing the blank cover and bottom insulator.

Figure 3. Installing the connecting straps.

GEH5581 Installation Instructions

R03

Rail Latch

Screw

Latch

Handle

Bottom Fiber

Insulator

Blank

Cover

Connecting

Strap

#10-32 x

1

/

2

"

Screw

Advertising
Table of contents