g

Spectra Series™ Power Panelboards

Circuit Breaker Cover

WARNING:

Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the
equipment or removing any component

.

Do

not remove circuit protective devices or any
other component until the power is turned
OFF.

General

These instructions apply to the following circuit breaker
frames: SE, SF, TE, TF, TQ, and TEL.

Installation

1. Select the breaker cover supports and breaker covers.

Table 1 lists the catalog numbers of the appropriate
cover supports for various switchboard and
panelboard sizes. Table 2 lists the breaker covers for
various breaker types.

Switchboard or Panelboard Width

Cover Height

27 & 31" Pnlbd

35" Swbd

36 & 40" Pnlbd

40" Swbd

44" Pnlbd
45" Swbd

4

1

/

8

" (3X) &

5

1

/

2

" (4X)

208C1850P4*

208C1850P3

208C1850P3

2

3

/

4

" (2X)

208C1850P6

208C1850P5

208C1850P5

• Use 208C1850P3 for SFHA, SFLA, SFPA, TFL, TFJ, TFK, and

THFK, in single-branch mountings.

Table 1. Circuit breaker cover support catalog numbers for various

panelboard and switchboard widths.

Switchboard or Panelboard Width

Cover Height

27 & 31" Pnlbd

35" Swbd

36 & 40" Pnlbd

40" Swbd

44" Pnlbd
45" Swbd

SEDA, SEHA, SELA, SEPA – Double-branch mount only

4

1

/

8

" (3X)

208C4262G32

208C4262G33

208C4262G34

5

1

/

2

" (4X)

N/A

208C4262G35

208C4262G36

SFHA, SFLA, SFPA – Single-branch mount (see Figure 1)

4

1

/

8

" (3X)

208C4262G53

208C4262G54

208C4262G55

5

1

/

2

" (4X)

N/A

208C4262G56

208C4262G57

SFHA, SFLA, SFPA – Double-branch mount

4

1

/

8

" (3X)

208C4262G58

208C4262G59

208C4262G60

51/2" (4X)

N/A

208C4262G61

208C4262G62

TEB, TED, THED, TEL – Double-branch mount

2

3

/

4

" (2X)

208C4262G26

208C4262G27

208C4262G28

4

1

/

8

" (3X)

208C4262G29

208C4262G30

208C4262G31

TFJ, TFK, THFK, TFL – Single-branch mount (see Figure 1)

4

1

/

8

" (3X)

208C4262G1

208C4262G2

208C4262G3

TFJ, TFK, THFK, TFL – Double-branch mount

4

1

/

8

" (3X)

N/A

208C4262G6

208C4262G7

TQD, THQD – Double-branch mount

2

3

/

4

" (2X)

208C4262G20

208C4262G21

208C4262G22

4

1

/

8

" (3X)

208C4262G23

208C4262G24

208C4262G25

Table 2. Circuit breaker cover catalog numbers for various

panelboard and switchboard widths.

2. Mount the circuit breaker cover supports.

Mount the

breaker cover supports supplied in the kit to the
circuit breaker module or mounting plate, according
to the instructions supplied with the module or
mounting plate.
To install the cover support for single-branch SF and
TF breakers, first remove the breaker mounting
bracket by prying back the plastic spring clip on the
module. Slide the cover support on and snap the
breaker mounting bracket back into the module.
Fasten the cover support to the module, as shown in
Figure 1.

Figure 1. Installing the cover support for single-branch SF and TF

breakers.

3. Attach the center barrier

to the breaker cover for

double-branch 3X or 4X TEB, TED, THED, TQD,
THQD, SE, SF, TFK, THFK, and TFL breakers. Use
two push-in rivets, as shown in Figure 2.

Figure 2. Attaching the center barrier to the breaker cover.

DEH042 Installation Instructions

R03

Cover

Support

Breaker

Mounting

Bracket

Advertising