GE Industrial Solutions AF-650 GP OPCGPIO General Purpose I_O Option Module User Manual

Page 3

Advertising
background image

1.2.1 Galvanic Isolation in the OPCGPIO

Digital/analog inputs are galvanically isolated from other inputs/outputs on the OPCGPIO and in the control card of the frequency converter. Digital/analogue
outputs in the OPCGPIO are galvanically isolated from other inputs/outputs on the OPCGPIO, but not from these on the control card of the drive.

If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is illustrated
in the drawing has to be established.

Illustration 1.2: Principle Diagram

AF-650 GP and AF-600 FP OPCGPIO General Purpose I/O Option Module