1.2.2 Digital inputs - Terminal X30/1-4

Parameters for set-up: E-53, E-54 and E-55

Number of digital
inputs

Voltage level

Voltage levels

Tolerance

Max. Input impedance

3

0-24 V DC

PNP type:
Common = 0 V
Logic “0”: Input < 5 V DC
Logic “0”: Input > 10 V DC
NPN type:
Common = 24 V
Logic “0”: Input > 19 V DC
Logic “0”: Input < 14 V DC

± 28 V continuous
± 37 V in minimum 10 sec.

Approx. 5 k ohm

1.2.3 Analog voltage inputs - Terminal X30/10-12

Parameters for set-up: AN-3#, AN-4# and DR-76

Number of analog voltage inputs

Standardized input signal

Tolerance

Resolution

Max. Input impedance

2

0-10 V DC

± 20 V continuously

10 bits

Approx. 5 K ohm

1.2.4 Digital outputs - Terminal X30/5-7

Parameters for set-up: E-56 and E-57

Number of digital outputs

Output level

Tolerance

Max.impedance

2

0 or 24 V DC

± 4 V

≥ 600 ohm

1.2.5 Analog outputs - Terminal X30/5-8

Parameters for set-up: AN-6# and DR-77

Number of analog outputs

Output signal level

Tolerance

Max.impedance

1

0/4 - 20 mA

± 0.1 mA

< 500 ohm

AF-650 GP and AF-600 FP OPCGPIO General Purpose I/O Option Module