GE Energy

CAR2548TN series rectifier

Input: 90Vac to 264Vac; Output: -54 Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A

April 23, 2013

©2012 General Electric Company. All rights reserved.

Page 3

-54V

dc

MAIN OUTPUT (continued)

Parameter

Device

Symbol

Min

Typ

Max

Unit

Remote ON/OFF delay time

All

40

ms

Turn-ON rise time (10 – 90% of V

out

)

All

60

ms

Transient response 50% step [10%-60%, 50% - 100%]

(dI/dt – 1A/µs, recovery 300µs)

All

V

out

-1350 +1350

mV

dc

Programmable range (hardware & software)

All

-45

-57

V

dc

Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)

All

-58 -59 -60 V

dc

Output current V

out

= -54V

dc

All

I

out

0

46.3

A

dc

Power limit 2500W

V

out

-42 -58 V

dc

Current limit, Hiccup (programmable level)

All

I

out

106

126

% of FL

Active current share

All

I

out

-5

+5

% of FL

AUXILIARY OUTPUT

Parameter

Device

Symbol

Min

Typ

Max

Unit

Set point

All

V

out

3.3

/

5.0

V

dc

Overall regulation (load, temperature, aging)

All

V

out

-5 +5 %

Ripple and noise

All

50

mVp-p

Output current

All

I

out

0 1

A

dc

Overload protection -

Overvoltage protection

Isolation Output/GND

All

100

V

dc

Environmental, Reliability

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature
Operating
Altitude Operating
Power Derating

-10

3

50

2250

2.5

°C

m

%/°C


Air inlet from sea level to 5,000 feet.
7400 ft
51°C to 70C

Storage
Altitude non-operating

-40

85

8200

°C

m


30,000 ft

Humidity Operating
Storage

30
10

95

95

%

Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3 20 -2000Hz, minimum 30 minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and tested

to meet NEBS specifications.

MTBF

100,000
200,000

Hrs

Full load, 50C ambient, per Bellcore RPP
Demonstrated


3

Designed to start at an ambient down to -40°C; meet spec after  30 min warm up period, may not meet operational limits below -10°C.