Introduction
Shunt Trip (Extended Range):
A device designed to switch the Power Circuit
Breaker OFF remotely. When energized a Shunt
Release instantaneously activates the circuit

breaker mechanism ensuring a rapid
disconnection of the main contacts. Shunt trips
are suitable for a continuous power supply and
are designed to be used as a closure prevention

device when energized. Two Shunt trips can be
mounted in each Power Circuit Breaker. The
device is available as factory mounted
component or as a field mountable device. It is an
easy-to-fit, clip-on unit, with simple plug-in

connectors to the Secondary Disconnect Block.

Table 1.Catalog Numbers and Ratings

Catalog No.

DC

Voltage AC Voltage

GSTG024R

24V

GSTG048R

48V

48V

GSTG072R

70-72V

GSTG120R

110-125V

120-127V

GSTG208AR

208V

GSTG240R

220V

240V

GSTG250DR

250V


DEH-41411 Installation Instructions

EntelliGuard

®

G Circuit Breaker

Accessories

Shunt Trip (Extended Range)




WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.




ƒ

Inrush Power: 480VA

ƒ

Steady state : 50VA


Use the following procedure to install the Shunt
Trip accessory into the circuit breaker.

1. Verify that the rating on the Shunt Trip
Mechanism identification plate matches the
voltage rating required for the application, as
listed in Table 1.



2. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the

breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement



3. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the

front cover over the handle to remove the front
cover as shown in Fig. 1.C

1

Advertising