Introduction

The Network Interlock provides a means of locking out a
circuit breaker to coordinate its operation with other
circuit breakers in the distribution network. When
activated by the EntelliGuard Messenger™, the Network
Interlock prevents the circuit breaker from closing. After
the EntelliGuard Messenger issues a reset signal, the
circuit breaker can be closed either remotely or locally.
The Network Interlock accessory includes a manual reset
lever to reset the device in the absence of a signal from the
EntelliGuard Messenger.

The Network Interlock contains a microswitch to remotely
indicate the state of the lockout and thus whether or not
the circuit breaker can be closed. The Network Interlock
kit (EGNTWKSFKIT) consists of the Network Interlock
module (EGNTWKSFRPLC), mounting plate, trip paddle
assembly, manual reset assembly, and hardware, as
illustrated in Figure 1. The catalog information for the
small frame Network Interlock kit and replacement
module is listed in Table 1.

Note: The Network Interlock kit is for use with
EntelliGuard

TM

circuit breakers installed in Entellisys™

Low Voltage Switchgear only.
Note: A Bell Alarm with Lockout and Network Interlock

cannot be installed concurrently in a circuit breaker.

Description

Catalog

Number

Voltage

Rating

60 Hz,

VAC

Inrush

current

A

Sealed

current

A

Complete Kit

(NI Module+

Mounting)

EGNTWKSFKIT

NI Module EGNTWKSFRPLC

120

6

1.43

Table 1. Catalog numbers and electrical ratings.

Figure 1. Network Interlock kit assembly (EGNTWKSFKIT).

Operation

The Network Interlock consists of a set solenoid, a reset

solenoid, and a status switch. The device connections to

the secondary disconnect are shown in Figure 2. When

voltage is applied across the set solenoid, the device locks

out the circuit breaker. Conversely, when voltage is applied

to the reset solenoid or when the manual reset button is

depressed, the Network Interlock allows the circuit breaker

to re-close.




Figure 2. Network Interlock connections to secondary disconnect.

(Contact shown in RESET state.)

g

EntelliGuard

TM

Power Circuit

BreakerAccessories

DEH41119 Installation Instructions

R01

Network Interlock for 800–2000 Ampere
Circuit Breakers

Trip Paddle
Assembly

Mounting plate

Manual Reset Assembly

Network Interlock

Module

(EGNTWKSFRPLC)

15

NI Set

Coil

20

16

21

19

NI Reset

Coil

NI Status

Contact

1

3

2

4

5

DEH41119 Installation Instructions R02