Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings

only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations
sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Device

Symbol

Min

Max

Unit

Input Voltage

Continuous All

V

IN

-0.3 80

V

dc

Transient, operational (≤100 ms)

All

V

IN,trans

-0.3 100

V

dc

Operating Ambient Temperature

All

T

A

-40 85

°C

Maximum Heat Plate Operating Temperature

-18H, H

T

C

-40 105

°C

(see Thermal Considerations section)

Storage Temperature

All

T

stg

-55 125

°C

Altitude* All

4000 m

I/O Isolation voltage (100% factory Hi-Pot tested)

All

2250 V

dc

* For higher altitude applications, contact your GE Sales Representative for alternative conditions of use.

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Operating Input Voltage

All

V

IN

18

24/48

75 V

dc

Maximum Input Current

All I

IN

7.3

7.8

A

dc

(V

IN

= V

IN, min

to V

IN, max

, V

O

= V

O, set

, I

O

=I

O, max

)

Input No Load Current

All I

IN,No load

120

80

mA

V

IN

= 24V

dc

, (I

O

= 0, module enabled)

V

IN

= 48V, (I

O

= 0, module enabled)

Input Stand-by Current

All

I

IN,stand-by

5

11

mA

(V

IN

= 24 to 48V, module disabled)

Inrush Transient

All

I

2

t

0.5

A

2

s

Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 12μH source impedance; V

IN, min

to V

IN, max,

I

O

= I

Omax

;

See Test configuration section)

All

30

mA

p-p

Input Ripple Rejection (120Hz)

All

60

dB

CAUTION: This power module is not internally fused. An input line fuse must always be used.

This power module can be used in a wide variety of applications, ranging from simple standalone operation to an integrated part
of sophisticated power architectures. To preserve maximum flexibility, internal fusing is not included, however, to achieve

maximum safety and system protection, always use an input line fuse. The safety agencies require a fast-acting fuse with a
maximum rating of 15 A (see Safety Considerations section). Based on the information provided in this data sheet on inrush energy
and maximum dc input current, the same type of fuse with a lower rating can be used. Refer to the fuse manufacturer’s data sheet

for further information.

Advertising