2020004403 (12/09) Page 8 of 18

The illustration shown above, provides a recommended method for grounding a separately

derived power system, per the National Electrical Code, Article 250.30. Please check with the

local municipality or governing authority for additional codes or other approved regulatory

requirements before attempting to configure any electrical power distribution system.

X2

X1

X3

X0

PHASE C

PHASE B

PHASE A

NEUTRAL

Bonding Jumper

Ref. NEC 250

-

30 (a) (1)

Grounding Electrode

Ref. NEC 250

-

30 (a) (4)

Primary Dist.

Panel w/Overcurrent

or Service Disconnect

Means

Grounding Electrode

Conductor Ref. NEC

250.62 - 250.64

-

250.66

GROUND

Equipment Grounding

Conductor Ref. NEC

250.32 (B) (1)

N

G

Note:

Primary transformer windings

not shown for simplicity

SPD

Example of an NEC Compliant Grounding Arrangement for a Separately Derived System