Spectra Series™ Power Panelboards

Ground Fault Neutral, 1200 A Maximum

WARNING: Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the

equipment or removing any component

.

Do

not remove circuit protective devices or any

other component until the power is turned

OFF.

Installation

1. Remove the connection bar. Loosen the four nuts on

the studs (two in each strap) located at the current

transformer and at the load end of the neutral, as

shown in Figure 1. Slide out the connection bar

assembly.

Figure 1. Removing the connection bar assembly.

2. Mount the neutral. Place the neutral in the desired

position in the end of the box stamped

LINE.

Mount it

on the studs in the back of the box. as shown in Figure

2. Place a flat washer, lock washer, and nut on the

studs, as shown in Figure 3. Leave the nuts hand tight.

Align the elongated holes in the neutral with the

holes in the box and secure with eight #10-32 x

7

/

8

"

thread-forming screws, as shown in Figure 4. Tighten

the screws and nuts to 27–32 in.-lb.

Figure 2. Neutral mounting position.

GEH5683 Installation Instructions

R02

Connection

Bar

Nuts

Current

Transformer

Load End

of Neutral

Stud (one

each side)