Figure 3. Mounting the neutral in the box.

Figure 4. Securing the neutral in position.

3. Mount the bond strap. If a bonding strap is required

for service entrance use, loosen the bolt at the line end

of the neutral transformer and slide the bond strap

under the head of the bolt, as shown in Figure 5. (For

NEMA 3R/12 enclosures go to step 4.) If the box is

painted, scratch through the paint in the area where

the bond strap is to contact the box. Secure the bond

strap to the box with one #10-32 x

3

/

8

" thread-forming

screw. Tighten the screws to 27–32 in.-lb. Retighten

the nut at the other end of the bond strap at the

neutral transformer to 200–250 in.-lb.

Figure 5. Attaching a bond strap.

#10 Flat Washer,

Lock Washer,

Hex Nut

Neutral

Base

Elongated

Hole

#10-32 x

7

/

8

" Screw

#10-32 x

3

/

8

" Screw

Bond

Strap

Slide Bond Strap

(with slot) under

Head of Bolt

Nut Washer (bolt

head on underside)