Car1248fp series rectifier, Data sheet, Input: 90v – GE Industrial Solutions CAR1248FP series User Manual

Page 8: Output: 48v, External eeprom

Advertising
background image

GE

Data Sheet

CAR1248FP series rectifier

Input: 90V

AC

to 264V

AC

; Output: 48V

DC

@ 1200W; 5 V

DC

@ 0.5A

February 26, 2013

©2013 General Electric Company. All rights reserved.

Page 8

V

OUT

[00]:

Output voltage read back, returns the voltage on

the anode side of the or’ing function, data LSB followed by
MSB.

The default value is 48V

DC

Example; readback 01EBh, convert into its decimal equivalent
and then multiply by the constant, V

OUT

= 491 x 0.102 =

50.08V

DC

I

OUT

[01]:

Output current read back, data LSB followed by MSB.

Example; readback 021Fh, convert into its decimal equivalent
and multiply by the constant, I

OUT

=543 x 0.042 = 22.8A

Temperature [02]:

Temperature read back, data LSB followed

by MSB.

Example; readback 037Bh, convert into its decimal equivalent
and multiply by the xonstant, temp = 891 x 0.0049 = 4.36. In
the table below this corresponds to 25C

Data

Temp

C

Data

Temp

C

Data

Temp

C

4.83 -5 3.71 45 1.7 95
4.78 0 3.51

50 1.54 100

4.72 5 3.3 55 1.4 105
4.65 10 3.09 60 1.26 110
4.56 15 2.88 65 1.14 115
4.46 20 2.67 70 1.03 120
4.35 25 2.46 75 0.93 125
4.21 30 2.25 80 0.84 130
4.06 35 2.06 85

3.89 40 1.88 90

ON/OFF [03]:

A logic ‘1’ turns OFF the 48V output of the

power supply.

Ilim [04]:

This feature lowers the current limit from the default

values of 02A8h (680), corresponding to 28.6A at high line and
0265h (613) corresponding to 25.8A at low line.

The delivered output current cannot exceed the maximum
power capacity of the unit. Thus, at high line the power supply
is limited to 1200W, thus, at 28.6A the output voltage is limited

to 41.96V

DC

,

Example: At high line, reduce the current limit to 20A.
Compute the data to be sent to the controller; 20 / 0.042 =

476. The hex equivalent of this decimal data is 01DCh. The
data should be sent across the bus as LSB [DC] followed by
MSB [01].

Vset [05]:

Changes the output voltage via i2c, if the Vprog

hardware signal is > 4V

DC

. If the Vprog pin voltage level is <

4V

DC

, this command is ignored.

The output voltage setting must be between 42.8 – 56V

DC

.

The default value is 01FEh, corresponding to 48V

DC

.

Example; set the output to 54V

DC

. Compute the data to be

sent to the controller; 54 / 0.094 = 574. The hex equivalent of
this decimal data is 023Eh. The data should be sent across the
bus as LSB [3E] followed by MSB [02].

Vprog [06];

Reads back the hardware configured analog

voltage program value via i2c.

The value can range from 0.364V to 3.27V.

Example: set the output to 44V

DC

. From the equation

determine that Vprog = 0.6. The 10bit D/A is set for the range
of 0 – 5V

DC

, therefore with a resolution of 1024 bits each bit is

0.00488V. So the corresponding value to enter is 0.6/0.00488 =
123 decimal. This corresponds to 7Bh. The data should be sent
across the bus as LSB [7B] followed by MSB [00].

OT trip[07] and OT recover[08];

Configures the OT shutdown

and recovery levels. The default values are;

OT trip: 120C corresponds to 1.03/0.00488 = D3h

OT recover: 110C that corresponds to 1.26/0.0049 = 0102h

Example: Change the recovery temperature to 100C. In the
look up table above the corresponding level is 1.54. Divide by
the conversion ration, 1.54/0.0049 = 315 dec. Converting to its
hex equivalent yields 013B hex. The data should be sent
across the bus as LSB [3B] followed by MSB [01].

DC_OK_HI[09] and DC_OK_LO[0A]:

Changes the DC_OK signal

comparator level. The default values are;

DC_OK_HI: 02CDh, corresponding to 67.5V
DC_OK_LO: 0133h, corresponding to 28.9V

Example: Change the upper level of comparison to 55V.
Determine the corresponding register value setting; 55/0.0941
= 584dec. This is equivalent to 0248h. The data should be
sent across the bus as LSB [48] followed by MSB [02].

STATUS [0B]:

All read backs are two bytes and so read back

two bytes but ignore the MSB.

Firmware [0C]:

Reads back the latest firmware revision.

MCUeeprom [0D – 7C]:

125 bytes of information may be

stored in the EEPROM section of the micro controller starting
from register location 0Dh. Each byte of data needs to be
stored into its specific register location, one byte at a time.

External EEPROM

A separate EEPROM, with its own i2c address and with

write_protect capability, provides 128 bytes of memory. This is
a standard i2c compliant generic EEPROM with a single byte
for its memory location. Standard i2c command structure

applies.

The following FRU_ID information is stored in this EEPROM

Start

Location

Length

Value

Description

00 7

Serial

number,

ascii

07 1

20

space

08

4

Date code [YYWW] ascii

0C 1

20

space

0D 17

Code CAR1248FPBXXXX1A ascii

1E 1

20

space

1F 1

Revision

Advertising