Car1248fp series rectifier, Data sheet, Input: 90v – GE Industrial Solutions CAR1248FP series User Manual

Page 9: Output: 48v, Leds, I/o expander option, Alarm table, Connector

Advertising
background image

GE

Data Sheet

CAR1248FP series rectifier

Input: 90V

AC

to 264V

AC

; Output: 48V

DC

@ 1200W; 5 V

DC

@ 0.5A

February 26, 2013

©2013 General Electric Company. All rights reserved.

Page 9

LEDs

Three LEDs are located on the front faceplate. The AC_OK LED
provides visual indication of the INPUT signal function. When
the LED is ON GREEN the power supply input is within normal
design limits.

When the DC_OK LED is GREEN the DC output is present.

When the FAULT_LED is RED then a fault condition exists and
the power supply may not provide output power. The table
below further defines these states:

I/O Expander option

The CAR1248FPx without extended i2c communications (blank
under the software option) has a single status/control byte I/O

expander that is accessible via address 0 x 4Eh (A2, A1, A0 are
pilled HI). This byte takes the form;

7

6

5

4

3

2

1

0

n/s n/s Fault ON/OFF Temp_OK n/s DCOK ACOK

n/s – not supported

Bits 0, 1, 3, and 5 are ‘read_only’ and are HI [1] during normal

operation. The rectifier needs to be biased externally in order to ‘read’
its operational state without the presence of input power.

Bit 4 is a ‘read/write’ bit that can be used to verify the ON/OFF
commanded state or change the commanded output of the rectifier.
In order to turn the output OFF this bit needs to be pulled LO [0].

No PEC support is provided. Standard i

2

c commands apply.

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

AC OK

DC OK

FAULT

FAULT

DC OK

AC OK

TEMP OK

1 Normal

Operation

Green

Green

OFF High High High

High

2

Low or NO INPUT

OFF

OFF

OFF

Low Low Low High

3 OVP

Green

OFF

Red

Low Low High High

4 Over

Current

Green

OFF

Red

High Low High High

5

Over Temp Fault

Green

OFF

Red

Low Low High Low

Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no AC.


Connector

FCI Berg P/N: 51939-070

Mating connector: FCI Berg P/N: 51915-050

Pin

Function

Pin

Function

Pin

Function

Pin

Function

A1 Vstb

B1 Fault C1 ISHARE

D1 VProg

A2

Vstb Return

B2

I Monitor (IMON)

C2

N/C

D2

OVP Test Point

A3

Signal Return

B3

Enable: “0” –ON “1” -OFF

C3

Over Temp Warning

D3

Remote ON/OFF

A4

Write Protect (WP)

B4

PS Present

C4

I

2

C Address (A0)

D4

DC OK

A5

Remote Sense (+)

B5

SDA (I

2

C bus)

C5

I

2

C Address (A1)

D5

AC OK

A6

Remote Sense (-)

B6

SCL (I

2

C bus)

C6

I

2

C Address (A2)

D6

Interrupt

P1 Line P2

Neutral P3 Chassis

P4 +V

OUT

P5

Output

Return