GE Industrial Solutions CR454A Series Starters User Manual

Definite purpose contactors & starters

Advertising
background image

Definite Purpose
Contactors & Starters

CR453A Series Contactors

CR454A Series Starters

Description

GE’s CR453A magnetic contactors provide a 2- or 3-pole

device for use in air conditioning units or other general

purpose applications. These instructions give information

about ratings, installation, accessories and wiring, overload

relay may be added if needed. Factory assembled starters

CR454A include overload relay

.

Motor branch circuit and control circuit overcurrent

protection should be supplied in accordance with the

National Electrical Code or local code as required. CR453A

contactors are suitable for use on a circuit capable of

delivering not more than 5,000 RMS symmetrical amperes,

600 volts maximum when protected by fuses or a circuit

breaker having an interrupting rating not less than 5,000

RMS symmetrical amperes.

Use 75° C copper conductors only.

Ratings – Full Voltage, Non-Reversing

Frame

Ratings

Resistive

Size

VAC

FLA

LRA

Horsepower

Rating Per

1 PH

3 PH

Pole

120

150

2

CR453AB

240

25

150

3

7.5

35

480

125

10

600

100

10

120

180

2

CR453AC

240

30

180

5

10

40

480

150

15

600

120

15

120

240

3

CR453AD

240

40

240

7.5

10

50

480

200

20

600

160

20

Caution: Before installing in a nuclear application, determine that the product is intended for such use.

Warning: Disconnect power before installing or servicing.

Typical CR453A Series contactor

Power Terminal Tightening Torque (lbs.-in.)

Terminal Type

Torque Values

Box Lug

40

Pressure Plate

20

Binding Screw

20