Contactor Installation

Before connecting to power supply:

1. Remove all packing.

2. Operate movable magnet and operating arm by

pressing down on the operating arm from the front

or side of the contactor to assure free movement.

3. Mount starter on a sturdy vertical support.

4. Make electrical connections as per wiring diagram.

For quick connect wiring, use UL recognized insulated

terminals.

Starter Installation

1. Remove all packing.

2. Motors with service factor of 1.15 or greater.

• Select overload relay as per the FLA shown in the

motor nameplate.

• Adjust the front mounted tripping current setting

dial to the motor FLA.

2. Motors with service factor less than 1.15

• Select overload relay as per the formula: Motor FLA

(shown in the motor plate) x 0.09.

• Adjust the front mounted tripping current setting dial

to the result of the above mentioned motor FLA.

3. Operate movable magnet and operating arm by pressing

down on the operating arm from the front or side of the

contactor to assure free movement.

4. Mount starter on a sturdy vertical support.

5. Make electrical connections as per wiring diagram.

For quick connect wiring, use UL recognized insulated

terminals.

6. Select the four modes by means of a front selector

lever.

7. Overload relays features tripping indicator, independent

& double break auxiliary tripping contacts (1NO+1NC)

with welding check lever.

8. Overload relay features thermal protection against

balanced overload, differential protection against

unbalanced overloads and also ambient temperature

compensation.

3.75
95,3

3.16
80,3

3.28
83,3

1.70
43,2

.35
8,9

MOUNTING HOLES FOR
#10 SCREWS(6 PLACES)

C

NC

N

C

NC

N

C

C

NC

N

NC

N

C

NC

N

NC

C

N

33

34 44

43

32 44

31 43

22

14

13

14

21

24

13 23

3 PHASE LINE CONNECTION

3 PHASE LINE CONNECTION

L1

L2

L2

T1

T2

T2

OPTIONAL
AUX
CONTACTS

NOMENCLATURE
M-LINE CONTACTOR
NO-NORMALLY OPEN
NC-NORMALLY CLOSED

AUX CONTACT OPTONS

TYPE

LEFT
SIDE

RIGHT
SIDE

1 SPDT

2 SPDT

2 NO

1 NO-1 NC

M

CONTROL
VOLTAGE

OPTIONAL
AUX
CONTACTS

FRONT VIEW

3.13
79,4

3.28
83,3

1.70
43,2

.24
6,0

2.25
57,0

1.71
43,3

3.87
98,2

5.68
144,3

.27
6,9

1.12
28,5

MOUNTING HOLES FOR
#10 SCREWS(6 PLACES)

Mounting Hole Dimensions

Contactor Wiring Diagram

CR454A Series Starter Dimensions