Finger Clusters (Assemblies) Accessory Manual DEH-41533 02/12

10. Tighten the jam nut to lock in the adjustment.

11. Clean finger assemblies, if necessary, with a clean, lint-free rag and isopropyl alcohol or

acetone.

12. Be sure to apply a thin film of Mobilgrease 28 (D50HD38) to the contact areas which slide onto

the switchgear stabs (See

Figure 5,

Step 2). This product is available in a 1-oz tube,

GE Part #193A1751P1.

Figure 5 summarizes the steps for working with the primary contacts.

Figure 5. Steps in Exploded Views

Advertising