3

Figure – 6

5

COIL KITS

5.1 Description
A wide range of coils is available for both electrically held and
mechanically held lighting contactor. Refer to the Ordering
Detail section for more information about the coil kit catalog
numbers and voltages available.

Note: For mechanically held lighting contactor, only use coil
rated up to 277 VAC maximum. Use control power
transformer for higher voltages.

5.2 Installation
1. Disconnect all power. Replace and mount the coil on the

contactor as shown in Figure 7.

2. For mechanically held contactors, remove all wires from

the control module and remove the coil cover along with
control module
.

Figure – 7

Table C

5.3 Wiring
Coil terminal can accept wires from #18 AWG to #14 AWG
(either solid or stranded) as single or combination of two wires
(Refer to Table C below for valid wire combination). Refer to
Table D below for required torque.

Table D

* #8 AWG is stranded only for the power pole.

Ordering details

Coil Kits:

CR460XCC

24V 60Hz /20V 50Hz coil

CR460XCD

28V 60Hz / 24V 50Hz coil

CR460XCJ

115-120V 60Hz / 110V 50Hz coil

CR460XCL

200-208V 60Hz coil

CR460XCS

230-240V 60Hz / 220V 50Hz coil

CR460XCN

265- 277V 60Hz / 240V 50Hz coil

CR460XCT

347V 60Hz coil

CR460XCU

460-480V 60Hz / 440V 50Hz coil

CR460XCY

575-600V 60Hz / 550V 50 Hz

Control Module Kits:

CR460XMB

2 wire 24 Vac 60/50 Hz

CR460XMC

2 wire 110-120 Vac 60/50 Hz

CR460XMD

2 wire 200-277 Vac 60/50 Hz

CR460XME

2 wire 12-18 Vdc

CR460XMM

3 wire 24 Vac 60/50 Hz

CR460XMN

3 wire 110-120 Vac 60/50 Hz

CR460XMP

3 wire 200-277 Vac 60/50 Hz

CR460XMR

3 wire 12-18 Vdc

Power Pole Kits:

CR460XP31

Single Power Pole

CR460XP32

Double Power Pole

Auxiliary Contact Kits:

CR460XB1

1 NO/NC

CR460XB2

2 NO/NC

Note

:

These instructions do not purport to cover all details or variations in

equipment nor to provide for every possible contingency to be met in
connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise which are not
covered sufficiently for the Purchaser’s purpose, the matter should be referred
to the nearest General Electric sales office.

#14 AWG

#16 AWG

#18 AWG

Size

Type

Solid Stranded Solid Stranded Solid Stranded

Solid

X

X

X

X

X

X

#14 AWG

Stranded

X

X

X

X

X

Solid

X

X

X

X

#16 AWG

Stranded

X

X

X

Solid

X

X

#18 AWG

Stranded

X