3 of 8, Dc output connections – lug type, Dc output connections – faston type – GE Industrial Solutions J85480S1, L20 – L29 Compact Power Line Shelves User Manual

Page 3

Advertising
background image

3 of 8

COMPACT POWER LINE SHELVES – MODEL J85480S1

Rear View - AC Input Connections / Split output concept

Tie_rap secured AC cables for IEC-320 inputs

DC Output Connections – Lug Type

 Each Output Bus is rated for

100A and up to 2 gage two-
hole lugs.

M6 nuts with conical washers

provided.

 Touch-Safe plastic covers

around output buses.

Torque to 50 in-lb
(5.7 Nm)

90° Lugs

DC Output Connections – FastON Type

 Three FastON blades are paralleled for

each output on either side of the shelf.
Each FastON carries 35 Amperes.

Each Set of blades carries up to 100

amperes output

-

+

-

+

Operation without a controller (output always ON jumpers)

Jumpers to short ENABLE (turn ON) to Logic_GRD
are either in a separate bag or inserted into the J1
signal connector.

Jumpers must be removed prior to inserting a
mating connector into the J1 housing.

Applications that desire a remote ON/OFF feature
should connect ENABLE-A to Logic_GRD via an
external switch. For split shelves ENABLE-A
control the two leftmost rectifiers and ENABLE-B
controls the two rightmost rectifiers.

Not required on L22 & L25 since these are
configured always ON.

1 3 5

2 4 6

29

30

Shorting jumper between J1-19 and J1-20
for single output shelves, and a second
shorting jumper between J1-21 and J1-22
for split output shelves
Part Number: AMP 881545-2 or equivalent
J1-19: ENABLE-A, J1-21 - ENABLE-B
J1-20, 22: Logic_GRD

J1

Rectifier
or
PEM

Feeder-A Feeder-B

AC or DC Input Feeds

Bus A
Output

Bus B

Output

Two DC Output Busses

Advertising