Set ground fault pick-up to 0.20, Relt test, Short time test – GE Industrial Solutions EntelliGuard G Digital Test Kit User Manual

Page 7

Advertising
background image

DEH-4568A Rev. 02 (08/09)

Trip Unit set-up for Testing RELT – Reduced Energy Let Through and Short Time

Change rating plug to a value approximately 50-60% of the breaker sensor,
see Table 1.0 on the following page

Set Long Time Pick-Up to 50% (allows test signal to cause O/L trip without extremely long time delay)

Set Long Time Delay to any of the lower bands

Set Short Time Pick-Up to 9X (set above expected test current)

Set Short Time Delay to any of the intermediate bands or set to OFF

Set Instantaneous Pick-Up > 5X (to prevent instantaneous trip with test kit input)

Set RELT Pick-Up for 1.5X

RECORD ALL TRIP UNIT
SETTINGS PRIOR TO TESTING

Set Ground Fault Pick-Up to 0.20

Set Ground Fault Delay to any of the upper delay bands

RELT Test

Reset Bell Alarm

Charge and Close Breaker

Turn RELT ON via local or remote RELT switch. Verify RELT light on instrument panel is ON

Press DISABLE GROUND FAULT button - verify LED is ON

Press OVERLOAD / GROUND FAULT button

Breaker trips

Bell alarm operates, if available

Event log (Event 0) registers instantaneous trip with magnitude of approx the RELT pick-up value

Short Time Test

To test Short Time function, set Short Time Pick-Up to 4X or less, set Instantaneous Pick-Up to >6X or OFF

Reset Bell Alarm

Charge and Close Breaker

Press DISABLE GROUND FAULT button - verify LED is ON

Turn RELT switch OFF. Verify RELT light on instrument panel is OFF

Press OVERLOAD / GROUND FAULT button

Breaker trips

Bell alarm operates, if available

Event log (Event 0) registers short time trip with magnitude of approx 1.5 times the sensor


RESTORE ALL TRIP UNIT SETTINGS AFTER TESTING IS COMPLETE AND REPLACE RATING PLUG WITH ORIGINAL