GE Industrial Solutions EntelliGuard G Digital Test Kit User Manual

Page 8

Advertising
background image

DEH-4568A Rev. 02 (08/09)

Table 1.0 Rating Plug selection for RELT and Short Time Test

Rating plug selection for testing RELT and Short Time with GTUTK20 test kit

Test current multiple for overcurrent tests **

Current

Sensor
(amps)

50%

Rating

Plug

(amps)

60%

Rating

Plug

(amps)

Use

Rating

Plug

(amps)

Sensor

Range

(amps)

%

Sensor

Equivalent

test current

signal from

test kit

(amps)

RELT &

Instantaneous

multiple

1

with

Test Rating

Plug

LT

multiple

2

when LT

pick-up =

0.5

ST

multiple

3

when LT

pick-up =

0.5

GF

multiple

4

when GF
pick-up =

0.2

400 200 240 200

200-400 50

600

3

6

6

7.5

800 400 480 400

400-1000 50

1200

3

6

6

7.5

1600 800 960 1000

1000-2500

63 2400

2.4

4.8 4.8 7.5

2000 1000 1200 1000

1000-2500

50 3000

3

6

6

7.5

2500

1250

1500

1500

1600-4000

60 3750

2.5

5

5

7.5

3000 1500 1800 1500

1600-4000

50 4500

3

6

6

7.5

3200 1600 1920 1500

1600-4000

47 4800

3.2

6.4 6.4 7.5

4000 2000 2400 2000

2000-5000

50 6000

3

6

6

7.5

5000 2500 3000 2500

2500-6400

50 7500

3

6

6

7.5

** Test kit provides a signal that is equivalent to 1.5x the current sensor value for a test current

1

Instantaneous pick-up is a multiple of the Rating Plug

2

Long time pick-up is a multiple of the Rating Plug

3

Short time pick-up is a multiple of Rating Plug * LT Pick-Up

4

Ground Fault is a multiple of the Current Sensor




RESTORE ALL TRIP UNIT SETTINGS AFTER TESTING IS COMPLETE AND REPLACE RATING PLUG WITH ORIGINAL





















GE
41 Woodford Avenue, Plainville, CT 06062
www.geelectrical.com
© 2008 General Electric Company