Arcing contacts assembly

Arcing contacts are supplied with the Entelliguard
breaker.


Fig A

Fig B

Contact

gap

Contact

gap

Table 1.

Arc contact Catalog and Ratings

Envelope Size Catalog #

TYPE

G20HARC H

type

Envelope 1

G20NARC S & N type

G40MARC H & M types

Envelope 2

G40NARC E & N types

Envelope 3 G64LARC













EntelliGuard

®

G

Circuit Breaker

Accessories

Arcing contacts assembly



WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.


AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement

Arcing contact assembly using cluster pliers:

1. Turn the breaker off and discharge the

closing springs by depressing the OFF and
ON buttons in the sequence OFF-ON-OFF.
Verify that the breaker OFF-ON indicator

shows OFF on a green background and
that the charge indicator shows
DISCHARGE on a white background. If
installing in a draw-out type breaker
remove breaker from adaptor (cassette)

before continuing.


2. The breaker should be safely isolated and

fully removed from the cassette (for

drawout breaker)

3. Loosen the mounting screws of arc

chamber to the housings as shown in fig
A

4. Lift the Arc chamber assembly as shown

in fig B.

5. Loosen the fixed arcing contact assembly

mounting screws as shown in fig C.

6. Inspect the arc plates & arcing contacts

and sides of the moldings for signs of

wear or damage. Replace as necessary.

DEH-41390 Installation Instructions

7. Close the circuit breaker & ensure the

contact gap between the fixed and
moving arcing contacts is set to 2.5mm as
shown in fig D

1