4 of 10, Dc output connections, Dc split output bus option – GE Industrial Solutions J85480S1, L1 – L14 Compact Power Line Shelves User Manual

Page 4: Controllerless operation

Advertising
background image

4 of 10

COMPACT POWER LINE SHELVES – MODEL J85480S1

Rectifier
or
PEM

Feeder-A Feeder-B

AC or DC Input
Feeds

Bus A
Output

Bus B
Output

Two DC Output
Busses

DC Output Connections

 Each Output Bus is rated for

100A and up to 2 gage two-
hole lugs.

M6 nuts with conical washers

provided.

 Touch-Safe plastic covers

around output buses.

Torque to 50 in-lb
(5.7 nm)

Torque to 50 in-lb
(5.7 nm)

DC Split Output Bus Option

 Split Vout ( - ) buses on either

side of the shelf. Vout ( + ) is
common to both sections.

 +5V bias maintains I

2

C

communications even during
a feeder fault.

 Multiple shelves may not be

paralleled together.

Controllerless Operation

 Lists 4 and 6 ship with a jumper

installed on connector J1 pins 21 and
23. This allows the shelf to be powered
without a controller. Remove this
jumper if controller cable installed.

 CP843A controller ships with a

connector that plugs into J1 on a List 1
shelf activating the controller.

Lists 7, 9 and 14 require cc848836107

connector be installed in J1 to allow the
shelf to power up without a controller.

L7, L9, L14 P1 Mating connector (pin out is standard 40 position like L4)

Type

Housing

Mating pin

Crimping tool

Individual wire set

AMP 102387-9 RoHS

20-24 awg: 6-87523-9

91517-1

22-26 awg: 6-87756-8

91517-1

40 position Ribbon cable

AMP 1658621-9 e/w 499252-1 (strain relief) RoHS

This connector set is different because it can accept either a ribbon cable or an individual wire mate.