GE Industrial Solutions EntelliGuard G Carriage Position Switch Kit User Manual

Entelliguard, G circuit breaker accessories, Carriage position switch kit

Advertising
background image

Introduction
Carriage Position Switch Kit:

Carriage position switch indicates the breaker
status whether it is in the Disconnect, Test or
Connected positions of a draw out circuit breaker.

The Carriage Position Switch comes in two
options: one switch or two switches per position.


Electrical characteristics Carriage Position
Switch Contacts

Table 1. Ratings.

AC Ratings

DC Ratings

Voltage Amps Voltage Amps

120V 10A 125V 0.5A
250V 10A 250V 0.25A

Contacts are Power Rated

Table2. Cat No.
GCPS1R

1 NO/1 NC per position

GCPS2R

2 NO/2 NC per position


The Switches are “change over switches” with NO,
NC & Com terminals. (Form C Contact).









DEH-41403 Installation Instructions



EntelliGuard

®

G Circuit Breaker

Accessories



Carriage Position Switch Kit







WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation , et décharger les

resorts d’armement


Use the following procedure to install the Position

Switch Kit accessory into the circuit breaker.

1. Verify that the rating and the catalogue on the

Position Switch Kit identification plate matches
the voltage rating required for the application,

as listed in Table 1


2. Before installing ensure the main power

sources are disconnected and no power to the

breaker main terminals


3. Rack out and remove the Breaker from

Cassette if it is installed

4. Insert the carriage position switch wires from

the opening from the inside of the cassette
and pull out as shown in Fig. 1

Figure 1. Wire insertion.

1

Advertising
Table of contents