Car0812dc series dc-dc converter, Data sheet, Input: -36v – GE Industrial Solutions CAR0812DC Series User Manual

Page 2: Output: +12 v, Or 5 v, Absolute maximum ratings, Electrical specifications

Advertising
background image

GE

Data Sheet

CAR0812DC Series DC-DC Converter

Input: -36V

DC

to -75V

DC

; Output: +12 V

DC

@ 850W; 3.3V

DC

or 5 V

DC

@ 1A

April 23, 2013

©2013 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations

sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Symbol

Min

Max

Unit

Input Voltage: Continuous

V

IN

+0.3 -75 V

DC

Operating Ambient Temperature

T

A

-10 70

1

°C

Storage Temperature

T

stg

-40 85 °C

I/O Isolation voltage (100% factory Hi-Pot tested)

1500

V

DC

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.

INPUT

Parameter

Symbol

Min

Typ

Max

Unit

Operational Range

V

IN

-36

-48/60

-75 V

DC

12V

DC

output turned OFF

V

IN

-32 -33 -35 V

DC

12V

DC

turned ON

V

IN

-33 -35 -36 V

DC

Maximum Input Current

I

IN

27.1

A

DC

(V

IN

= -36V

DC

, V

OUT

= V

O, set

, I

OUT

=I

O, max

)

Cold Start Inrush Current

I

IN

40

A

peak

(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency (T

AMB

=25C, V

IN

=-48V

DC

, V

OUT

=12V

DC

)

10% load

80

%

20% load

88

50% load

92

100% load

89

Holdup time – 12V

DC

(Tamb 25C, V

IN

-48V

DC

, C

ext

5,000µf)

T 2

2

ms

Isolation T

AMB

=25C, V

IN

=-48V

DC

, V

OUT

=12V

DC

- Input/Output

1500

V

DC

Input/Frame

1500

1 minute per IEC/EN 60950-1) Output/Frame

100

Ground lug

Connection required to meet EMI performance

12V

dc

MAIN OUTPUT

Parameter

Symbol

Min

Typ

Max

Unit

Output power

P

OUT

0 850

W

DC

Set point

V

OUT

11.98 12.00 12.02 V

DC

Overall regulation (load, temperature, aging)

-3

+3

%

Ripple and noise

3

120

mV

p-p

Turn-ON overshoot

+3

%

Turn-ON delay

T

2

sec

1

Derated above 50C at 2.5%/C

2

Full load, with 5,000µf external capacitance, 12Vdc set point, droop to 10.8Vdc permitted, > -48Vdc input

3

Measured across a 10µf tantalum and a 0.1µf ceramic capacitors in parallel. For V

in

> 60V

dc

the PARD is relaxed to 150mV

p-p

.

Advertising