CAR0812DC Series DC-DC Converter

Input: -36V

DC

to -75V

DC

; Output: +12 V

DC

@ 850W; 3.3V

DC

or 5 V

DC

@ 1A

April 23, 2013

©2013 General Electric Company. All rights reserved.

Page 8

Characteristic Curves (continued)

The following figures provide typical characteristics for the CAR0812DC converter at 25

o

C

CU

RRE

NT

V

O

(V

) (20

0mV/d

iv)

I

O

(I) (2

0A/d

iv)

V

O

(V

) (2

0m

V/div)

I

O

(I)

(5

00

mA/

div)

TIME, t (2ms/div)

TIME, t (50ms/div)

Figure 7. 12V transient response for 10 to 60% step load,

Vin: -48V

DC

, slew rate 1A/µs.

Figure 7. 12V transient response for 10 to 60% step load, Vin:

-48V

DC

, slew rate 1A/µs.

Vout

Iout

Iout

Total (A)

Iout

unit #1 (A)

Iout

unit #2 (A) Ishare

11.968

25%

35.47

18.54

16.93

1.13%

11.96

30%

42.51

22.07

20.44

1.15%

11.923

50%

70.4

36.09

34.31

1.25%

11.877

75%

106

54.25

51.75

1.76%

11.831

100%

140.86

71.65

69.21

1.72%

Vout

Iout

Iout

Total (A)

Iout

DC unit (A)

Iout

AC unit (A) Ishare

11.972

25%

35.32

17.71

17.61

0.07%

11.965

30%

42.4

21.43

20.97

0.32%

11.925

50%

69.91

34.07

35.84

1.25%

11.878

75%

104.74

50.81

53.93

2.20%

11.831

100%

140.09

68.99

71.1

1.49%

Vin = 48Vdc

Vin = 48Vdc

Table 9. Current share accuracy among two CAR0812DC
units

Table 10. Current share accuracy among a CAR0812AC and a
CAR0812DC unit

(-10°C)

25°C

50°C

Turn ON point (V)

35

34.9

34.9

Turn OFF point (V)

32.7

32.7

32.7

Hysteresis (V)

2.3

2.2

2.2

NO LOAD

(-10°C)

25°C

50°C

Turn ON point (V)

35.8

35.6

35.5

Turn OFF point (V)

33.3

33.5

33.4

Hysteresis (V)

2.5

2.1

2.1

FULL LOAD

Table 11. Input under voltage protection – no load

Table 12. Input under voltage protection – full load

RT3 (actual temperature)

Full load 50°C ambient

75°C

Half load 70C ambient

79.1C

Protect point

95C

Recovery point

79C

Table 13. Over-temperature protection; Actual temperature

readings and protection levels.