Event menu – GE Industrial Solutions A Series Lighting Control Panelboards Handheld Programmer ASRGLCHPK User Manual

Page 2

Advertising
background image

7

Application ....................................................................................................4

Menu Structure ............................................................................................4

Menu Descriptions.......................................................................................4

Schedules .............................................................................................................................................. 4
Calendar ............................................................................................................................................... 4
I/O Menu ............................................................................................................................................. 4
Lighting Group.................................................................................................................................... 4
Dimming Menu ................................................................................................................................... 4
Burn Hours Menu ............................................................................................................................... 4
Breaker Override Menu ..................................................................................................................... 4
Configuration Menu........................................................................................................................... 4
Event Menu .......................................................................................................................................... 3

Set Password.

This function sets the

password for the current user.

Reset MSP430.

This function resets the

back plane of the controller. Note that
this item should only be used for instant
remapping of the breaker or for
diagnostic purposes.

Reconfig Net.

T h i s

f u n c t i o n

reconfigures the controller’s address
using DNA. This is done when the
controller is first connected to the
network; since it is a subnet device, it
inherits the address of the master above.
For example, if the master address is 100
and the address of the subnet is 1,
Reconfig Net sets the address to 101.

Reset Device.

This function performs a

hardware reset of the controller.

Save Flash.

This function saves the

changes made to flash memory so they
can be reloaded if the battery goes dead
or to return to the previous version.

Load Flash.

This function loads the

database with the last version saved to
flash memory. It overwrites the current
contents of the database and performs a
hardware reset.

Event Menu

These menu items are used to
acknowledge alarms, view battery status,
view or reset the CE Log, and set up the
CE Log. The CE log captures the events
listed in Table 1.

Event

Display

Alarm

ALARM

Alarm Acknowledged ALARM ACK

Dead Battery

DEAD BATT

Dead Battery
Restored

DEAD BATT
RESTORED

Command Failure

CMD FAIL

Command Fail
Restored

CMD FAIL
RESTORED

Status ON

STATUS ON

Status OFF

STATUS OFF

Under Voltage

UNDER VOLT

Under Voltage
Restored

UNDER VOLT
RESTORED

Reset

DEV RESET

Time / Date change

TIME CHG

DB Load

DB LOAD

DB Save

DB SAVE

DB Clear

DB CLEAR

Lnk Online

DEV ONLINE

Lnk Offline

DEV OFFLINE

Breaker Trip

BREAKER TRIP

Breaker Trip
Restored

BREAKER TRIP
RESTORED

No events occurred

NONE

Table 1. Events captured in the CE Log.