3

Lighting Group

These menu items are used to view or
edit Zn 1–16 groups and to turn them
on or off manually.

Outputs.

This function links breakers

and/or lighting groups to the group
output. It also assigns a specific switch
input (analog or digital) to each breaker
or group.

Schedule.

This function turns the group

on and off according to a set schedule.

Astro.

This function links Astro time to

turn the group on and off.

Photocell.

This function turns the group

on and off with analog or digital inputs.

Override.

This function overrides the

group from off to on for a set time.

Groups.

This function turns the group

on or off when all nested groups turn on
or off, following OR logic.

Dimming Menu

These menu items are used to view
and/or edit the dimming modules that
can be optionally attached to the
product (Linknet devices 6 and 7) to
control the lighting ballast. The input to
these modules is a photocell (AI) and
the output is the analog output (AV).

Dim Mod 600 Submenu.

These functions

adjust each control loop for dimming
module 1 with Linknet device 6. There
are eight control loops on a board and
each consists of the following functions:

Ltg Lvl (input) – the input from
the photocell

Ltg SP – the set light level

Ltg OP

Ltg PB (controller PB) – the
proportional gain of the feedback
loop

Ltg RR (controller rest rate) – the
integral gain of the feedback loop
and the

Dim Mod 700 Submenu.

These functions

are the same as Dim Mod 600 but for
Linknet device 7.

Burn Hours Menu

This function is used to view and/or
reset the breaker burn/run hours for an
individual breaker.

Breaker Override Menu

This function views the Override BV for
each breaker. Override is used to turn an
individual breaker on for a set time and
then shut it off. It is used for integration
but not by default.

Configuration Menu

These menu items are used to configure
the lighting controller and system.

Set Time.

This function sets the time

and date of the controller.

Device Information.

This function

provides information about the device,
such as the device name, model number,
firmware version build, and software
version.

Device Menu.

This function sets up the

location and daylight savings time.

Application

This is the quick start guide for the
Handheld Programmer (cat. no.
ASRGLCHPK) for the A Series

®

Lighting Controller.

Menu Structure

The Handheld Programmer has two
modes of operation, depending on the
permission level of the user. Figure 1
shows the sequence of menus for display-
only mode and Figure 2 shows the
sequence for full-editing mode. The
default password in display-only mode is
1234 and in full-editing mode is 4129.

Menu Descriptions

Following are brief descriptions of the
menu items and the functions they
provide.

Schedules

This function views or edits Zn 1–16
schedules and turns them on or off
manually. Up to eight turn on/off times
can be scheduled per day for each day of
the week and two calendar references.

Calendar

This function views or edits the
Calendar reference, which is used to
select days of the year. Calendar is
referenced in the schedule object and
when the controller date matches the
calendar date, the schedule follows the
calendar on and off times.

I/O Menu

These menu items view and/or edit the
inputs and outputs.

Odd Breakers.

The odd breakers are

those numbered 1, 3, 5, …, 65. These
functions provide the following:

Commissioning

Manually turning on or off

Linking override inputs

Assigning override times

Enabling event logging for breaker
on, breaker off, tripped breaker,
and command failure

Direct/reverse feedback setting

Enabling flick warning

Setting the time of flick warning

Determining the status of the odd
breakers

Even Breakers.

The even breakers are

those numbered 2, 4, …, 66. These
functions provide the same operations
as those of Odd Breakers.

Lighting Switches.

This function is used

to manually turn the switches on or off
and to commission them.

Analog Input.

This function finds the

value/status of the three analog inputs
on the controller and to commission
them.

Breaker Test.

This function tests the

breakers for a set time.