Feature description – GE Industrial Solutions EQW006 Series User Manual

Page 9

Advertising
background image

Data Sheet

July 27, 2011

EQW006 Series, Eight Brick Power Modules: DC-DC Converter

36 – 75Vdc Input; 12Vdc Output; 6A Output Current

LINEAGE

POWER

9

Feature Description

Remote On/Off

Two remote on/off options are available. Positive logic
turns the module on during a logic high voltage on the
ON/OFF pin, and off during a logic low. Negative logic
remote On/Off, device code suffix “1”, turns the
module off during a logic high and on during a logic
low.

ON/OFF

Vin+

Vin-

I

on/off

V

on/off

Vout+

TRIM

Vout-

Figure 10. Remote On/Off Implementation.

To turn the power module on and off, the user must
supply a switch (open collector or equivalent) to
control the voltage (V

on/off

) between the ON/OFF

terminal and the V

IN

(-) terminal (see Figure 10). Logic

low is 0V ≤ V

on/off

≤ 1.2V. The maximum I

on/off

during a

logic low is 1mA, the switch should be maintain a
logic low level whilst sinking this current.
During a logic high, the typical maximum V

on/off

generated by the module is 15V, and the maximum
allowable leakage current at V

on/off

= 5V is 1μA.

If not using the remote on/off feature:
For positive logic, leave the ON/OFF pin open.
For negative logic, short the ON/OFF pin to V

IN

(-).

Remote Sense

Remote sense minimizes the effects of distribution
losses by regulating the voltage at the remote-sense
connections (See Figure 11). The voltage between
the remote-sense pins and the output terminals must
not exceed the output voltage sense range given in
the Feature Specifications table:
[VO(+) – VO(–)] – [SENSE(+) – SENSE(–)]

 0.5 V

Although the output voltage can be increased by both
the remote sense and by the trim, the maximum
increase for the output voltage is not the sum of both.
The maximum increase is the larger of either the
remote sense or the trim.

The amount of power delivered by the module is
defined as the voltage at the output terminals
multiplied by the output current. When using remote
sense and trim, the output voltage of the module can
be increased, which at the same output current would
increase the power output of the module. Care should
be taken to ensure that the maximum output power of
the module remains at or below the maximum rated
power (Maximum rated power = Vo,set x Io,max).

V

O

(+)

SENSE(+)

SENSE(–)

V

O

(–)

V

I

(+)

V

I

(-)

I

O

LOAD

CONTACT AND

DISTRIBUTION LOSSE

SUPPLY

I

I

CONTACT

RESISTANCE

Figure 11. Circuit Configuration for remote
sense .

Input Undervoltage Lockout

At input voltages below the input undervoltage lockout
limit, the module operation is disabled. The module
will only begin to operate once the input voltage is
raised above the undervoltage lockout turn-on
threshold, V

UV/ON

.

Once operating, the module will continue to operate
until the input voltage is taken below the undervoltage
turn-off threshold, V

UV/OFF

.

Overtemperature Protection

To provide protection under certain fault conditions,
the unit is equipped with a thermal shutdown circuit.
The unit will shutdown if the thermal reference point
Tref (Figure 14), exceeds 110

o

C (typical), but the

thermal shutdown is not intended as a guarantee that
the unit will survive temperatures beyond its rating.
The module will automatically restarts after it cools
down.

Output Overvoltage Protection

The output overvoltage protection consists of circuitry
that internally clamps the output voltage. If a more
accurate output overvoltage protection scheme is
required then this should be implemented externally
via use of the remote on/off pin.

Advertising