Cassette Envelope 2 – 3200A ANSI

Terminal assemblies are supplied with the
Entelliguard breaker.



































Back Connected Terminations Assembly (3 Pole)
Procedure:

1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green

background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
cassette before continuing.

2. Assemble the middle bottom and top Back

Connected Termination assemblies first to the
cassette back terminal support as shown in Fig A.

3. Middle Terminal assemblies to be tightened with

M10 hardware’s as shown in Fig A, to 40 Nm (29.5
ft-lbs) torque.

4. Assemble the heat sinks LH & RH with spacers

introduced in between the multiple pads of
terminal assemblies as shown in Fig B for bottom
& top sides. Tightened them with M8 mounting
hardware’s to 16 Nm (11.8 ft-lbs) torque.

5. Assemble the outer terminal assemblies on

bottom and top side with M10 hardware
tightened to 40 Nm (29.5 ft-lbs) torque as shown
in Fig C.

6. Assemble the heat sinks RH with clearance holes

& spacers introduced in between the multiple
pads of outer terminal assemblies as shown in fig

D, for bottom & top sides and tightened them

Envelope Size

Catalog #

Description

TYPE

GBB232TBC3

Top side

3 pole

GBB232BBC3

Bottom side

3 pole

GBB232TBC4

Top side

4 pole

Envelope 2

GBB232BBC4

Bottom side

4 pole

EntelliGuard

®

G

Circuit Breaker

Accessories
Back Connected Terminations for
Cassette

WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation, et décharger les

resorts d’armement

DEH-41434 Installation Instructions

Fig A. Back Connected Terminations, (Middle
pole) for 3200 Amperes (ANSI) 3 pole

Table 1. Back Connected Terminations