Undervoltage Release:
A device designed to open the breaker contacts

and to prevent the breaker from closing when in
a ‘No volt’ condition. On a de-energization the
Undervoltage release activates the circuit breaker
mechanism and ensures a rapid disconnection of
the main contacts and the device prevents the

Power Circuit Breaker from closing. The
EntelliGuard G™ Undervoltage release is
designed to react within a pre-defined Voltage
band, only reacting when the voltage supply
drops below the limits of this band. To prevent

nuisance tripping due to short power
interruptions or ‘Brown Outs’ the device has a
built in delay of 50 Milliseconds when Voltage is at
or below 50% of rated Voltage. Two under

voltage Releases can be mounted in each Power
Circuit Breaker.

Table 1.

Catalog No DC Voltage AC Voltage

GUVT024DR

24V

GUVT030DR

30V

GUVT048R

48V

48V

GUVT060DR

60-72V

GUVT120R

110-130V

120-130V

GUVT208AR

208V

GUVT240R

220-240V

220-240V

GUVT277R

250V

250-277V




DEH-41410 Installation Instructions

EntelliGuard

®

G Circuit Breaker

Accessories

Undervoltage Release


WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.





For an External Time Delay Module (1-3 second
delay) refer to Pub DEH-41406

ƒ

Inrush Power: 350VA

ƒ

Steady state : 40VA

Use the following procedure to install the

Undervoltage Device accessory into the circuit
breaker.

1. Verify that the rating on the Undervoltage
Device identification plate matches the voltage

rating required for the application, as listed in
Table 1.


2. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows

DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement


3. Loosen the 6 screws on front cover (fascia)

using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.C.

1