GE Industrial Solutions EntelliGuard G Back Connected Terminations for Envelope 2, 3200A ANSI, Fixed type User Manual

Entelliguard

Advertising
background image

Back Connected Terminations
Envelope 2, 3200A ANSI, Fixed type

Terminal assemblies are supplied with the
Entelliguard breaker. Fixed breakers have Back or
Front Connected Terminations available. This
instruction is for Back Connected Terminations


































Back Connected Terminations Assembly (3 Pole)
Procedure:
1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows

DISCHARGE on a white background.

2. First assemble & orient the middle terminations

assemblies on to the breaker rear terminals as
shown in Fig A.

3. Middle top & bottom terminal assemblies to be

tightened with M12 hardware’s as shown in Fig A,
to 80 Nm (59 ft-lbs) torque.

4. Assemble the heat sinks LH & RH with spacers

introduced in between the multiple pads of
terminal assemblies as shown in Fig B for bottom

& top sides. Tightened them with M8 mounting
hardware’s to 16 Nm (11.8 ft-lbs) torque.

5. Assemble the outer terminal assemblies on

bottom and top side with M12 hardware
tightened to 80 Nm (59 ft-lbs) torque as shown in
Fig C.

6. Assemble the heat sinks RH with clearance holes

& spacers introduced in between the multiple

pads of outer terminal assemblies as shown in fig
D, for bottom & top sides and tightened them
with M8 mounting hardware’s to 16 Nm (11.8 ft-
lbs) torque.

Envelope

Size

Catalog #

Description

TYPE

GBB232TBB3

Top side

3 pole

GBB232BBB3

Bottom side

3 pole

GBB232TBB4

Top side

4 pole

Envelope 2

GBB232BBB3

Bottom side

4 pole

EntelliGuard

®

G

Circuit Breaker

Accessories
Back Connected Terminations for
Fixed Breaker

WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation, et décharger les

resorts d’armement

DEH- 41443 Installation Instructions

M12 Mtg
Hardware

M12 Spring
washer

M12 Plain
washer

Nut plate

Bottom terminal
assembly

Top terminal
assembly

M12 Mtg
Hardware

M12 Spring
washer

M12 Plain
washer

Nut plate

Bottom termin
assembly

Top terminal
assembly

al

Fig A. Back Connected Terminations assembly, (Middle pole)
For 3200 Amperes (ANSI) 3 pole, fixed type

Table 1. Back Connected Terminations

Catalog numbers

1

Advertising