7. Assemble remaining terminal assemblies similarly

on all poles so as to populate as 3pole / 4 pole
breaker.

8. The bus bars to be supported within 200mm

distance and tightened to 80Nm (59 ft-lbs) torque.









































































Top Heat sink LH
(with clearance hole)

Top Heat sink RH
(with tapping)

M8, Mtg
hardware

Top Spacer

Bottom Heat sink RH
(with tapping)

Bottom Heat sink LH
(with clearance hole)

Bottom Spacer

Top Heat sink LH
(with clearance hole)

Top Heat sink RH
(with tapping)

M8, Mtg
hardware

Top Spacer

Bottom Heat sink RH
(with tapping)

Bottom Heat sink LH
(with clearance hole)

Bottom Spacer

M12 Mtg
hardwares

Top terminal
assembly

Bottom terminal
assembly

M12 Mtg
hardwares

Top terminal
assembly

Bottom terminal
assembly

Fig B. Heat sink Asm with spacers (Middle pole)
For 3200A , (ANSI) 3 pole, fixed type


Fig

C.

Outer pole, Back Connected Terminations

asm For 3200 A, (ANSI) 3 Pole, fixed type

Top Heat sink (RH)
(with clearance hole)

M8, Mtg
hardware

M8, Nuts

Top Spacer

Top Heat sink (RH)
(with clearance hole)

M8, Mtg
hardware

M8, Nuts

Top Spacer

Fig

D.

Outer pole Heat Sink with spacer assembly

For 3200 Amperes (ANSI), 3 Pole, Fixed type