Introduction
Wall mounting Kit:

Wall mounting kit is offered for Fixed version of

Envelope 1 & 2 Breakers

Kit consists of LH and RH mouniting plates to be
fixed in to the Breaker.


Catalog Number:

Catalog No Description
GFMTG

Wall Mounting kit


Use the following procedure to install the Wall
mounting brackets.

1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in

the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing

in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing


2. Loosen the 6 screws on front cover (fascia)

using a pozidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.










DEH-41383 Installation Instructions

EntelliGuard

®

G Circuit Breaker


Accessories

Wall mounting Kit




WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement


Figure 1. (A) Front Cover (B) Screw Removal (C) Handle

Rotation


3. Remove the mounting plate which is

assembled to the breaker by removing the fixing
screws as shown in Fig. 2.

Fixing screws

Figure 2.