Clusters:

These are the main isolating contacts which are
fitted to the rear terminals on the moving portion
of the with drawable unit
As part of standard inspection and maintenance

procedures, cluster contacts have been
designed to be easily and quickly removed and
replaced using cluster pliers. These clusters are
mounted horizontally and vertically thru cluster
pads for different envelope sizes. The slot is

provided on the terminals for locking the
clusters. For higher current and short circuit
ratings the clusters are assembled parallel.

Table 1. Cluster Catalog and Ratings

Envelope

Size

Catalog #

Current

Rating

Envelope 1 G20NCLS

2000A

G20MCLS

2000A

Envelope 2

G32ECLS

3200A

Envelope 3 G64LCLS

6000A








DEH-41460 Installation Instructions

EntelliGuard

®

G

Circuit Breaker




Clusters

:

Accessories






WARNING: Before installing any accessories,

turn the breaker OFF, disconnect it from all
voltage sources, and discharge the closing

spings.

AVERTISSEMENT: Avant d’installer tout

accessoire, mettre le disjoncteur en position

OFF, le déconnecter de toute tension
d’alimentation , et décharger les resorts

d’armement

Removal of Cluster assembly using cluster
pliers:

1. Turn the breaker off and discharge the

closing springs by depressing the OFF and
ON buttons in the sequence OFF-ON-OFF.
Verify that the breaker OFF-ON indicator

shows OFF on a green background and
that the charge indicator shows
DISCHARGE on a white background. If
installing in a draw-out type breaker
remove breaker from adaptor (cassette)

before continuing.

2. The breaker should be safely isolated and

fully removed from the cassette/panel.

3. Inspect the rear cluster contacts for signs

of overheating and wear and replace if
necessary.

4. Hold & position the cluster plier jaws on

the cluster fingers of the cluster finger
assembly at the rear ends.

5. Press the extended handles of the cluster

plier assembly such that the cluster

assembly becomes loose on the rear
terminals.

1

Advertising