Step 4, Adjustments

SMR1 digital RMS trip unit: Features a fixed

instantaneous trip function and an adjustable trip

function Im, which can shorten the trip time to

approximately 100ms, for over current above 2x

to 13x. To set the Im value, using switch dial,

select a specific value of St. See figure 3. The St

set point value is a multiple of the installed rating

plug - rated current (Ir),

Im = St x Ir.

Step 5, Circuit breaker performance and

operation

The breaker contact status is indicated by the

handle position, and the positions are marked on

either side of the handle escutcheon, clearly

showing the status of the breaker contacts. ON

and/or I indicate breaker is ON and OFF and/or O

indicate breaker is OFF.

The breaker tripped position

is indicated by the symbol.

To close the breaker from the OFF position moves

the handle to the ON position. To close the

breaker from the trip position, first move the

handle fully to the OFF (reset) position then to the

ON position. See Figure 6.

A Push-To-Trip button is provided for convenience

of testing the mechanical trip operation of the

breaker.

The Push-To-Trip should be tested annually.

Caution: Automatic tripping of the circuit breaker

may indicate a system problem. Identify and

correct any problem before turning the device on

again.

Important: Le declenchement automatique de

disjoncteru, peut indiquer un probleme de circuit.

Identifiez et corrigez le probleme avant de

refermer l'appareil.


Terminal (IP20) covers,

Line and load

Figure 5, Setting adjustment, tamper resistant cover
and terminal (IP20) cover

Figure 6 - Mechanically
Operating Circuit breaker

Figure 3, SMR1 trip unit St (2x –13x), Im = St x Ir

St Dial